Technical data

Appendix
A.1 Standards, Approvals, Certificates, Guidelines, Labels, and Declarations
TS Adapter II
Manual, 06/2008, A5E00272728-03
49
cULus approval, Hazardous Location
cULus Listed 7RA9 INT. CONT. EQ. FOR HAZ. LOC.
Underwriters Laboratories Inc., to
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 142 (Process Control Equipment)
UL 1604 (Hazardous Location)
CSA-213 (Hazardous Location)
APPROVED for Use in
Cl. 1, Div. 2, GP. A, B, C, D T4A
Cl. 1, Zone 2, GP. IIC T4
Note
The system installation must be compliant with NEC (National Electric Code)
requirements.
For use in Class I, Division 2 environments, the TS Adapter II must be installed in a
cubicle with minimum IP54 protection to IEC 60529.
Information on use of the TS Adapter II in Zone 2 hazardous areas is contained in the
"Product Information ATEX Zone 2.pdf" file,
This file is located on the product CD in the "_Product_Information" folder.
WARNING
Explosion Hazard - Do not disconnect while circuit is live unless area is known to be
non-hazardous.
Explosion Hazard - Substitution of components may impair suitability for Class I,
Division 2 or Class I, Zone 2.