Technical data
Appendix
A.1 Standards, Approvals, Certificates, Guidelines, Labels, and Declarations
TS Adapter II
Manual, 06/2008, A5E00272728-03
49
cULus approval, Hazardous Location
cULus Listed 7RA9 INT. CONT. EQ. FOR HAZ. LOC.
Underwriters Laboratories Inc., to
● UL 508 (Industrial Control Equipment)
● CSA C22.2 No. 142 (Process Control Equipment)
● UL 1604 (Hazardous Location)
● CSA-213 (Hazardous Location)
APPROVED for Use in
● Cl. 1, Div. 2, GP. A, B, C, D T4A
● Cl. 1, Zone 2, GP. IIC T4
Note
The system installation must be compliant with NEC (National Electric Code)
requirements.
For use in Class I, Division 2 environments, the TS Adapter II must be installed in a
cubicle with minimum IP54 protection to IEC 60529.
Information on use of the TS Adapter II in Zone 2 hazardous areas is contained in the
"Product Information ATEX Zone 2.pdf" file,
This file is located on the product CD in the "_Product_Information" folder.
WARNING
Explosion Hazard - Do not disconnect while circuit is live unless area is known to be
non-hazardous.
Explosion Hazard - Substitution of components may impair suitability for Class I,
Division 2 or Class I, Zone 2.