Specifications
158 Siemens Simatic S7 Driver Online Help
To configure the driver from Database Manager, you must know the following
information about the driver:
• The three-letter acronym for the driver. For the SI7 driver, the acronym is SI7.
• The names of the field devices or process hardware that you want to collect
data from, as defined in the driver configuration.
• The registers in the device that you want to collect data from.
• The type of signal conditioning you want to apply to the data.
• The specific digital point in the register you want to access. This information
is only necessary for digital database blocks configured with the BYTE data
type. The SI7 driver accepts bit values from 0 to 7.
Datablocks are automatically created for devices that already exist in the Power Tool
when the Auto Create option is enabled. Devices are not automatically created.
Remember that the Driver field in Database Manager accepts the three-letter driver
acronym. The I/O Address field uses the device name assigned in the Power Tool
followed by the location in the device.
Refer to Entering Driver Information in Database Manager for details on entering
driver data in Database Manager for automatic datablock creation.
IMPORTANT: Always stop any 7.x driver you have running before you import a
database, reload a database, or create multiple database blocks with the Generate
command. If you leave the driver running while you complete any of these tasks, the
database may not load or import properly, or you may have to restart FIX/iFIX or
Database Manager.
See Also
Specifying the I/O Driver in Database Manager | Specifying I/O Addresses in
Database Manager | Specifying Signal Conditioning in Database Manager |
Specifying Hardware Options in Database Manager