A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
319
350000 - GUI alarms
Number Effect/causes Remedy
350000 PROFIsafe packages have not arrived within the
necessary period.
There is a communication problem with the F-CPU.
RT is terminated
Check the WLAN connection.
350001 PROFIsafe packages have not arrived within the
necessary period.
There is a communication problem with the F-CPU.
The PROFIsafe connection is re-established.
Check the WLAN connection.
350002 An internal error has occurred.
Runtime is terminated
Internal error
350003 Feedback concerning the connection established with
the F-CPU.
The Emergency-Off buttons are active immediately.
--
350004 PROFIsafe communication was set and the
connection was cleared.
The Runtime can be terminated.
The Emergency-Off buttons are deactivated
immediately.
--
350005 Incorrect address configured for the F-slave.
No PROFIsafe connection.
Check and modify the address of the F slave in
WinCC flexible ES.
350006 The acknowledgement buttons in the
"Acknowledgement" and "Panic" functions were not
tested before logging on.
It is not possible to log onto the effective range.
Press the two acknowledgement buttons one after
another in the "Acknowledgement" and "Panic"
positions.
350008 The wrong number of failsafe buttons was configured.
No PROFIsafe connection.
Change the number of failsafe buttons in the project.
350009 The device is in Override mode.
It may no longer be possible to detect the location
because transponder detection fails.
Exit Override mode.
350010 Internal error: The device has no failsafe buttons. Send the device back.