Operating instructions
Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
318 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Number Effect/causes Remedy
320005 The project contains ProAgent elements which are not
installed. ProAgent diagnostic functions cannot be
performed
In order to run the project, install the optional
ProAgent package.
320006 You have attempted to execute a function which is not
supported in the current constellation.
Check the type of the selected unit.
320007 No error-triggering addresses were found on the
networks.
ProAgent cannot indicate any faulty addresses.
Switch the detail screen to STL layout mode and
check the status of the addresses and exclusion
addresses.
320008 The diagnostic data stored in the configuration are not
synchronized with those in the PLC.
ProAgent can only indicate the diagnostic units.
Transfer the project to the HMI device again.
320009 The diagnostic data stored in the configuration are not
synchronized with those in the PLC. The diagnostic
screens can be operated as usual.
ProAgent may be unable to show all diagnostic texts.
Transfer the project to the HMI device again.
320010 The diagnostic data stored in the configuration are not
synchronized with those in STEP7.
The ProAgent diagnostics data is not up-to-date.
Transfer the project to the HMI device again.
320011 A unit with the corresponding DB number and FB
number does not exist.
The function cannot be executed.
Check the parameters of the "SelectUnit" function
and the units selected in the project.
320012 The "Step sequence mode" dialog is no longer
supported.
Use the ZP_STEP step sequence screen from the
corresponding standard project for your project.
Instead of calling the
Overview_Step_Sequence_Mode function, call the
"FixedScreenSelection" function using ZP_STEP as
the screen name.
320014 The selected PLC cannot be evaluated for ProAgent.
The Alarm view assigned to the
"EvaluateAlarmDisplayFault" system function could
not be found.
Check the parameters of the
"EvaluateAlarmDisplayFault" system function.
330000 - GUI alarms
Number Effect/causes Remedy
330022 Too many dialogs are open on the HMI device. Close all dialogs you do not require on the HMI
device.
330026 The password will expire after the number of days
shown.
Enter a new password.