Operating instructions
Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
317
Number Effect/causes Remedy
290110 The default values could not be set due to an error. --
290111 The Recipes subsystem cannot be used. Recipe
views have no content and recipe-specific functions
will not be performed.
Possible causes:
• An error occurred while transferring the recipes.
• The recipe structure was changed in ES. When
the project was downloaded again, the recipes
were not transferred with it. This means that the
new configuration data is not being transferred to
the old recipes on the device.
Transfer the project to the device again, together
with the recipes (the corresponding check box in the
Transfer dialog must be checked).
300000 - Alarm_S alarms
Number Effect/causes Remedy
300000 Faulty configuration of process monitoring (e.g. using
PDiag or S7-Graph): More alarms are queued than
specified in the specifications of the CPU. No further
ALARM_S alarms can be managed by the PLC and
reported to the HMI devices.
Change the PLC configuration.
300001 ALARM_S is not registered on this PLC. Select a controller that supports the ALARM_S
service.
310000 - Report system alarms
Number Effect/causes Remedy
310000 An attempt is being made to print too many reports in
parallel.
Only one log file can be output to the printer at a given
time; the print job is therefore rejected.
Wait until the previous active log was printed.
Repeat the print job if necessary.
310001 An error occurred on triggering the printer. The report
is either not printed or printed with errors.
Evaluate the additional system alarms related to this
alarm.
Repeat the print job if necessary.
320000 - Alarms
Number Effect/causes Remedy
320000 The movements have already been indicated by
another device.
The movements can no longer be controlled.
Deselect the movements on the other display units
and select the motion control screen on the required
display unit.
320001 The network is too complex.
The faulty addresses cannot be indicated.
View the network in STL.
320002 No diagnosable alarm message (error) selected.
The unit associated with the alarm message could not
be selected.
Select a diagnostics alarm from the ZP_ALARM
alarm screen.
320003 No alarm message (error) exists for the selected unit.
The detail view cannot visualize any networks.
Select the defective unit from the overview screen.
320004 The required signal states could not be read by the
PLC. The faulty addresses cannot be found.
Check the consistency between the configuration on
the display unit and the PLC program.