Operating instructions

Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
314 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Number Effect/causes Remedy
290007 There is a difference between the source and target
structure of the recipe currently being processed. The
target structure contains an additional data recipe tag
which is not available in the source structure.
The data recipe tag specified is assigned its start
value.
Insert the specified data recipe tag in the source
structure.
290008 There is a difference between the source and target
structure of the recipe currently being processed. The
source structure contains an additional data recipe tag
which is not available in the target structure and
therefore cannot be assigned.
The value is rejected.
Remove the specified data recipe tag in the specified
recipe from the project.
290010 The storage location configured for the recipe is not
permitted.
Possible causes:
Illegal characters, write protection, data carrier out of
space or does not exist.
Check the configured storage location.
290011 The record with the specified number does not exist. Check the source for the number (constant or tag
value)
290012 The recipe with the specified number does not exist. Check the source for the number (constant or tag
value)
290013 An attempt was made to save a record under a record
number which already exists.
The action is not executed.
The following remedies are available:
Check the source for the number (constant or tag
value)
First, delete the record
Change the "Overwrite" function parameter
290014 The file specified to be imported could not be found. Check:
The file name
Ensure that the file is in the specified directory
290020 Alarm reporting that the download of records from the
HMI device to the PLC has started.
--
290021 Alarm reporting that the download of records from the
HMI device to the PLC was completed.
--
290022 Alarm reporting that the download of records from the
HMI device to the PLC was canceled due to an error.
Check in the configuration whether:
The tag addresses are configured in the PLC
The recipe number exists
The record number exist
The "Overwrite" function parameter is set
290023 Alarm reporting that the download of records from the
PLC to the HMI device has started.
--
290024 Alarm reporting that the download of records from the
PLC to the HMI device was completed.
---
290025 Alarm reporting that the download of records from the
PLC to the HMI device was canceled due to an error.
Check in the configuration whether:
The tag addresses are configured in the PLC
The recipe number exists
The record number exist
The "Overwrite" function parameter is set