A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
311
Number Effect/causes Remedy
260025 The password you entered does not meet the
necessary security guidelines.
Enter a password that contains at least one special
character.
260028 Upon system start-up, an attempt to log on, or when
trying to change the password of a SIMATIC log-on
user, the system attempts to access the SIMATIC
Logon Server.
If attempting to log on, the new user is not logged in. If
a different user was logged on before, then this user
is logged off.
Check the connection to the SIMATIC Logon Server
and its configuration; for example:
1. Port number
2. IP address
3. Server name
4. Functional transfer cable
Or use a local user.
260029 The SIMATIC Logon user is not associated to any or
several groups.
The new user is not logged in. If a different user was
logged on before, then this user is logged off.
Check the user data on the SIMATIC Logon Server
and the configuration in your WinCC flexible project.
A user may only be assigned to one group.
260030 The SIMATIC Logon user could not change his
password on the SIMATIC Logon Server. The new
password may not comply with the password
regulations on the server or the user does not have
the right to change his password.
The old password remains and the user is logged off.
Log in again and choose a different password.
Check the password rules on the SIMATIC Logon
Server.
260031 It was not possible to log the user on to the SIMATIC
Logon Server. The user name or the password could
be incorrect or the user does not have sufficient rights
to log on.
The new user is not logged in. If a different user was
logged on before, then this user is logged off.
Try again. If necessary, check the password data on
the SIMATIC Logon Server.
260032 It was not possible to log the user on to the SIMATIC
Logon Server as his account is blocked.
The new user is not logged in. If a different user was
logged on before, then this user is logged off.
Check the user data on the SIMATIC Logon Server.
260033 The action change password or log on user could not
be carried out.
Check the configuration of the SIMATIC Logon
Server.
260034 The last logon operation has not yet ended. A user
action or a logon dialog can therefore not be called.
The logon dialog is not opened. The user action is not
executed.
Wait until the logon operation is complete.
260035 The last attempt to change the password was not
completed. A user action or a logon dialog can
therefore not be called.
The logon dialog is not opened. The user action is not
executed.
Wait until the procedure is complete.
260036 There are insufficient licenses on the SIMATIC Logon
Sever. The logon is not authorized.
Check the licensing on the SIMATIC Logon Server.
260037 There is no license on the SIMATIC Logon Sever. A
logon is not possible.
It is not possible to log on via the SIMATIC Logon
Server, only via a local user.
Check the licensing on the SIMATIC Logon Server.