Operating instructions
Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
310 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Number Effect/causes Remedy
250002 The tag in the specified line in "Status Force" is not
updated because it is not possible to map the PLC
type in the tag type.
Check the set address.
250003 An attempt to connect to the PLC failed. The tags are
not updated.
Check the connection to the PLC. Check that the
PLC is switched on and is online.
260000 - Password system alarms
Number Effect/causes Remedy
260000 An unknown user or an unknown password has been
entered in the system.
The current user is logged off from the system.
Log on to the system as a user with a valid
password.
260001 The logged in user does not have sufficient
authorization to execute the protected functions on
the system.
Log on to the system as a user with sufficient
authorization.
260002 This alarm is triggered by the system function
"TrackUserChange".
--
260003 The user has logged off from the system. --
260004 The user name entered into the user view already
exists in the user management.
Select another user name because user names have
to be unique in the user management.
260005 The entry is discarded. Enter a shorter user name.
260006 The entry is discarded. Use a shorter or longer password.
260007 The logon timeout value entered is outside the valid
range of 0 to 60 minutes.
The new value is discarded and the original value is
retained.
Enter a logon timeout value between 0 and 60
minutes.
260008 An attempt was made to read a PTProRun.pwl file
created with ProTool V 6.0 in WinCC flexible.
Reading the file was canceled due to incompatibility of
the format.
--
260009 You have attempted to delete the user "Admin" or
"PLC User". These users are fixed components of the
user management and cannot be deleted.
If you need to delete a user, because perhaps you
have exceeded the maximum number permitted,
delete another user.
260012 The passwords entered in the "Change Password"
dialog and the confirmation field are not identical.
The password has not been changed. User will be
logged off.
You have to log on to the system again. Then enter
the identical password twice to be able to change the
password.
260013 The password entered in the "Change Password"
dialog is invalid because it is already in use.
The password has not been changed. User will be
logged off.
You have to log on to the system again. Then enter
a new password that has not been used before.
260014 You have tried unsuccessfully to log on 3 times in
succession.
You will be locked out and assigned to group no. 0.
You can log on to the system with your correct
password. Only an administrator can change the
assignment to a group.
260023 The password you entered does not meet the
necessary security guidelines.
Enter a password that contains at least one number.
260024 The password you entered does not meet the
necessary security guidelines.
Enter a password that contains at least one
character.