Operating instructions

Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
309
Number Effect/causes Remedy
230306 Error in the connection to the remote server. This may
occur as a result of network problems.
The attempt to connect failed.
Check whether
The bus cable is plugged in
There are network problems
230307 The connection to the remote server was shut down
because
The remote server was shut down, or
The user instructed the server to close all
connections
The connection is closed.
--
230308 This alarm provides information on the connection
status.
An attempt is made to connect.
--
240000 - Authorization alarms
Number Effect/causes Remedy
240000 WinCC flexible Runtime is operating in demo mode.
You have no authorization or your authorization is
corrupted.
Install the authorization.
240001 WinCC flexible Runtime is operating in demo mode.
Too many tags are configured for the installed
version.
Load an adequate authorization / powerpack.
240002 WinCC flexible Runtime is operating with a time-
limited emergency authorization.
Restore the full authorization.
240004 Error while reading the emergency authorization.
WinCC flexible Runtime is operating in demo mode.
Restart WinCC flexible Runtime, install the
authorization or repair the authorization (see
Commissioning Instructions Software Protection).
240005 The Automation License Manager has detected an
internal system fault.
Possible causes:
A corrupt file
A defective installation
No free space for the Automation License
Manager etc.
Reboot the HMI device or PC. If this does not solve
the problem, remove the Automation License
Manager and install it again.
250000 - S7 Force alarms
Number Effect/causes Remedy
250000 The tag in the specified line in "Status Force" is not
updated because the address configured for this tag
is not available.
Check the set address and then verify that the
address is set up in the PLC.
250001 The tag in the specified line in "Status Force" is not
updated because the PLC type configured for this tag
does not exist.
Check the set address.