A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
305
190100 - Area pointer alarms
Number Effect/causes Remedy
190100 The area pointer is not updated because the
address configured for this pointer does not exist.
Type
1 Warnings
2 Errors
3 PLC acknowledgment
4 HMI device acknowledgment
5 LED mapping
6 Trend request
7 Trend transfer 1
8 Trend transfer 2
No.:
Consecutive number displayed in WinCC flexible
ES.
Check the configuration.
190101 The area pointer is not updated because it is not
possible to map the PLC type to the area pointer
type.
Parameter type and no.:
see alarm 190100
--
190102 The area pointer is updated after the cause of the
last error state has been eliminated (return to
normal operation). Parameter type and no.: See
alarm 190100.
--
200000 - PLC coordination alarms
Number Effect/causes Remedy
200000 Coordination is not executed because the address
configured in the PLC does not exist/is not set.
Change the address or set up the address in the PLC.
200001 Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
Change the address or set the address in the PLC at an
area which allows write access.
200002 Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
Internal error
200003 Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
--
200004 The coordination may not be executed. --
200005 No more data is read or written. Possible causes:
• The cable is defective
• The PLC does not respond, is defective, etc.
• System overload
Ensure that the cable is plugged in and the PLC is
operational.
Restart the system if the system alarm persists.