Operating instructions

Overview
1.7 Functional scope with WinCC flexible
MP 377, MP 377 PRO (WinCC flexible)
30 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Screens
Object Specification MP 377
Quantity 500
Fields per screen 200
Tags per screen 400
Complex objects per screen
(for example, bars)
20
Screens
Template Yes
Recipes
Object Specification MP 377
Quantity 500
Data records per recipe 1000
Entries per recipe 1000
Recipe memory 128 Kb
Recipes
Location
1)
Memory card
USB memory stick
Network drive
1)
The number of recipe data records might be restricted by the capacity of the
storage medium.
Logs
Note
The HMI devices are suitable for the logging of relatively small volumes of data.
Manage the data in several adjacent archives in a segmented circular log. The use of a large
circular log has a negative effect on performance.
Object Specification MP 377
Number of logs 50
Number of partial logs in a segmented
circular log
400
Entries per log 10 000
Filing format CSV with ANSI
character set
Logs
Location
1)
Memory card
USB memory stick
Network drive
1)
The number of entries in the log may be restricted by the capacity of the
storage medium.