Operating instructions

Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
297
Number Effect/causes Remedy
80045 The export of a log was interrupted due to an error
in the connection to the server or at the server
itself.
The export is repeated automatically. Check:
The connection to the server
If the server is running
If there is enough free space on the server
80046 The destination file could not be written while
exporting the log.
Check whether there is enough space on the server
and it you have permission to create the log file.
80047 The log could not be read while exporting it. Check whether the storage medium is correctly
inserted.
80049 The log could not be renamed while preparing to
export it.
The job can not be completed."
Check whether the storage medium is correctly
inserted and if there is sufficient space on the medium.
80050 The log which shall be exported is not closed.
The job can not be completed.
Make sure the "CloseAll Logs" system function is
called before using the "ExportLog" system function.
Change the configuration as required.
90000 - FDA alarms
Number Effect/causes Remedy
90024 No operator actions can be logged due to lack of
space on the storage medium for log. The operator
action will therefore not be executed.
Make more space available by inserting an empty
storage medium or swapping out the log files on the
server using "ExportLog".
90025 No user actions can be logged because of error
state of the archive. Therefore the user action will
not be executed.
Check whether the storage medium is correctly
inserted.
90026 No operator actions can be logged because the log
is closed. The operator action will therefore not be
executed.
Before further operator actions are carried out, the log
must be opened again using the system function
"OpenAllLogs". Change the configuration as required.
90028 The password you entered is incorrect. Enter the correct password.
90029 Runtime was closed during ongoing operation
(perhaps due to a power failure) or a storage
medium in use is incompatible with Audit Trail. An
Audit Trail is not suitable if it belongs to another
project or has already be archived.
Ensure that you are using the correct storage medium.
90030 Runtime was closed during ongoing operation
(perhaps due to a power failure).
--
90031 Runtime was closed during ongoing operation
(perhaps due to a power failure).
--
90032 Running out of space on the storage medium
for log.
Make more space available by inserting an empty
storage medium or swapping out the log files on the
server using "ExportLog".
90033 No more space on the storage medium for log. As
of now, no more operator actions requiring logging
will be executed.
Make more space available by inserting an empty
storage medium or swapping out the log files on the
server using "ExportLog".
90039 You do not have the necessary authorization to
perform this action.
Adapt or upgrade your authorizations.
90040 Audit Trail is switched off because of a forced user
action.
Activate the "Audit Trail" again using the system
function "StartLog".