Operating instructions

Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
294 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Number Effect/causes Remedy
70036 No SMTP server for sending e-mails is configured.
An attempt to connect to an SMTP server has
failed and it is not possible to send e-mails.
WinCC flexible Runtime generates the system
alarm after the first attempt to send an e-mail.
Configure an SMTP server:
In WinCC flexible Engineering System
using "Device settings > Device settings"
In the Windows CE operating system
using "Control Panel > Internet Settings > E-mail >
SMTP Server"
70037 An e-mail cannot be sent for unknown reasons.
The contents of the e-mail are lost.
Check the e-mail parameters (recipient etc.).
70038 The SMTP server has rejected sending or
forwarding an e-mail because the domain of the
recipient is unknown to the server or because the
SMTP server requires authentication.
The contents of the e-mail are lost.
Check the domain of the recipient address or
deactivate the authentication on the SMTP server if
possible. SMTP authentication is currently not used in
WinCC flexible Runtime.
70039 The syntax of the e-mail address is incorrect or
contains illegal characters.
The contents of the e-mail are discarded.
Check the e-mail address of the recipient.
70040 The syntax of the e-mail address is incorrect or
contains illegal characters.
--
70041 The import of the user management was aborted
due to an error.
Nothing was imported.
Check your user management or transfer it again to
the panel.
70042 The value range for the tags has been exceeded
while executing the system function.
The system function calculation has not been
carried out.
Check the desired calculation and correct it
if necessary.
70043 The value range for the tags has been exceeded
while executing the system function.
The system function calculation has not been
carried out.
Check the desired calculation and correct it
if necessary.
80000 - Archive alarms
Number Effect/causes Remedy
80001 The log specified is filled to the size defined (in
percent) and must be stored elsewhere.
Store the file or table by executing a ‘move’ or ‘copy’
function.
80002 A line is missing in the specified log. --
80003 The copying process for logging was not
successful.
In this case, it is advisable to check any
subsequent system alarms, too.
--
80006 Since logging is not possible, this causes a
permanent loss of the functionality.
In the case of databases, check whether the
corresponding data source exists and start up the
system again.
80009 A copying action has been completed successfully. --
80010 Since the storage location was incorrectly entered
in WinCC flexible, this causes a permanent loss of
the functionality.
Configure the storage location for the respective log
again and restart the system when the full functionality
is required.