Operating instructions
Appendix
A.2 System alarms
MP 377, MP 377 PRO (WinCC flexible)
292 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
70000 - Win32 function alarms
Number Effect/causes Remedy
70010 The application could not be started because it
could not be found in the path specified or there is
insufficient memory space.
Check whether the application exists in the specified
path or close other applications.
70011 The system time could not be modified.
The error alarm only appears in connection with
area pointer "Date/time PLC". Possible causes:
• An invalid time was transferred in the job
mailbox.
• The Windows user has no right to modify the
system time.
If the first parameter in the system alarm is
displayed with the value 13, the second parameter
indicates the byte containing the incorrect value.
Check the time which is to be set.
Using Windows NT/2000/XP: The user executing
WinCC flexible Runtime must be granted the right to
change the system time of the operating system.
70012 An error occurred when executing the function
"StopRuntime" with the option "Runtime and
operating system".
Windows and WinCC flexible Runtime are not
closed.
One possible cause is that other programs cannot
be closed.
Close all programs currently running.
Then close Windows.
70013 The system time could not be modified because an
invalid value was entered. Incorrect separators may
have been used.
Check the time which is to be set.
70014 The system time could not be modified. Possible
causes:
• An invalid time was transferred.
• The Windows user has no right to modify the
system time.
Windows rejects the setting request.
Check the time which is to be set.
Using Windows NT/2000/XP: The user executing
WinCC flexible Runtime must be granted the right to
change the system time of the operating system.
70015 The system time could not be read because
Windows rejects the reading function.
--
70016 An attempt was made to select a screen by means
of a system function or job. This is not possible
because the screen number specified does not
exist.
Or: A screen could not be generated due to
insufficient system memory.
Or: The screen is blocked.
Or: Screen call has not been executed correctly.
Check the screen number in the function or job with the
screen numbers configured.
Assign the number to a screen if necessary.
Check the details for the screen call and whether the
screen is blocked for specific users.
70017 Date/time is not read from the area pointer because
the address set in the PLC is either not available or
has not been set up.
Change the address or set up the address in the PLC.
70018 Acknowledgment that the password list has been
successfully imported.
--
70019 Acknowledgment that the password list has been
successfully exported.
--
70020 Acknowledgment for activation of alarm reporting. --
70021 Acknowledgment for deactivation of alarm
reporting.
--