Operating instructions

Commissioning a project
7.7 Updating the operating system
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
177
7.7.5 Resetting to factory settings with WinCC flexible
Requirements
No project is open on the configuring PC in WinCC flexible.
The HMI device is connected to this configuration PC over the standard Ethernet cable.
Have the MAC address of the Ethernet interface on your HMI device to hand.
The MAC address is displayed briefly when the HMI device is turned on.
The MAC address is displayed in the "PROFINET" dialog in the Control Panel.
Procedure - Setting the PC interface
1. Select "Start > Control Panel > Set PG / PC interface" on the configuration PC.
2. Select "S7ONLINE (STEP7) -> TCP / IP" from the "Application access point" area.
3. Select the interface which is connected to the HMI device from the "Interface
parameterization used" area.
4. Confirm your entries.