Operating instructions

Commissioning a project
7.6 Backup and restore
MP 377, MP 377 PRO (WinCC flexible)
168 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
Procedure
In "Online" mode, you can test individual project functions on the HMI device without them
being affected by the PLC. PLC tags are updated in this case.
You have the option to test all communication-dependent functions, for example alarms, etc.
Test the operating elements and views of the project.
7.6 Backup and restore
7.6.1 Overview
Backup and restore
You can back up and restore the following data in the internal flash memory of the
HMI device with a PC:
Project and HMI device image
Password list
Recipe data
License keys
Use one of the following tools for backup and restore:
WinCC flexible
ProSave
Note
Alternatively, use the control panel to back up to an external memory device.
General information
NOTICE
Power failure
If a complete restore operation is interrupted due to power failure on the HMI device, the
operating system of the HMI device may be deleted! In this case, you have to reset the HMI
device to its factory settings.
Compatibility conflict
If a message is output on the HMI device warning of a compatibility conflict during the
restore operation, the operating system must be updated.
See also
Saving to external storage device (backup) (Page 153)