Operating instructions

Configuring the operating system
6.14 Changing transfer settings
MP 377, MP 377 PRO (WinCC flexible)
Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
137
NOTICE
"Remote control" for "Channel 1"
If the "Remote Control" check box is activated during "Online" operating mode, the X10 port
cannot be used for communication.
The "Remote Control" check box must be deactivated for "Online" operating mode. Once
the serial transfer is complete, in the "Channel 1" group you must therefore deactivate the
"Remote Control" check box.
Transfer mode using "Channel 2"
When the project on the HMI device starts, transfer parameters, e.g. HMI device address,
for MPI/PROFIBUS DP are overwritten with the values from the project.
You can change the settings for the transfer via "Channel 2".
The following steps are required:
Close the project.
Change the settings on the HMI device.
Then return to "Transfer" mode.
The next time the project is started on the HMI device, the settings will be overwritten by
the values from the project.
Note
If the HMI device is in "Transfer" mode while changes are made to the transfer settings,
the settings only go into effect after the transfer function is restarted.
This may occur if the Control Panel is opened to change the transfer properties in
an active project.