Operating instructions
Configuring the operating system
6.13 Enabling PROFINET IO
MP 377, MP 377 PRO (WinCC flexible)
134 Operating Instructions, 10/2008, 6AV6691-1DR01-0AB0
6.13 Enabling PROFINET IO
PROFINET IO
If the HMI device is connected to the PLC via PROFINET, function keys or buttons, for
example, can be configured as PROFINET IO direct keys. If PROFINET IO direct keys are
used in the project, they must be enabled.
Note
If you enable PROFINET IO direct keys, you cannot use the RS 422/RS 485 port
for serial communication.
PROFINET IO direct keys and PROFIBUS DP direct keys are mutually exclusive.
Requirements
You have opened the "PROFINET" dialog with the "PROFINET" icon.
① Activating or deactivating the PROFINET IO direct keys
② Text box for the device name
③ MAC address of the HMI device
NOTICE
Inconsistent device name
If the device name does not match the device name entered in the HW Config of STEP 7,
the direct keys do not work.
Use the device name from the HW Config of STEP 7. This device name does not
correspond to the device name used under Windows CE.