Operating instructions
Table Of Contents
- SIMATIC IPC627C
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety notes
- 3 Description
- 4 Application planning
- 5 Mounting
- 6 Connecting
- 7 Commissioning
- 8 Integration
- 9 Functions
- 10 Expansion and parameter assignment
- 11 Service and maintenance
- 11.1 Removing and installing hardware components
- 11.1.1 Repairs
- 11.1.2 Preventive maintenance
- 11.1.3 Replacing the Backup Battery
- 11.1.4 Removing/Installing the Power Supply
- 11.1.5 Installing / removing the bus board
- 11.1.6 Installing / removing the motherboard
- 11.1.7 Installing / removing the equipment fan
- 11.1.8 Installing / removing the power supply fan
- 11.1.9 Processor replacement
- 11.2 Reinstalling the software
- 11.2.1 General installation procedure
- 11.2.2 Restoring the Factory State of the Software Using the Restore DVD
- 11.2.3 Installing Windows
- 11.2.4 Setting up the language selection by means of the Multilanguage User Interface (MUI)
- 11.2.5 Recovery of Windows 7
- 11.2.6 Installing drivers and software
- 11.2.7 Installing the RAID Controller software
- 11.2.8 Installing the optional burner or DVD software
- 11.2.9 Update installation
- 11.2.10 Data backup / subsequent modification of partitions
- 11.2.11 CP 1616 onboard
- 11.3 Installing the RAID Controller software
- 11.4 BIOS update
- 11.5 BIOS Recovery
- 11.1 Removing and installing hardware components
- 12 Alarm, error, and system messages
- 13 Troubleshooting/FAQs
- 14 Technical data
- 15 Dimension drawings
- 16 Detailed descriptions
- A Appendix
- B ESD guidelines
- C List of abbreviations
- Glossary
- Index

Connecting
6.2 Connecting the 100 - 240 V AC Power Supply
SIMATIC IPC627C
38 Operating Instructions, 11/2010, A5E02669068-02
6.2 Connecting the 100 - 240 V AC Power Supply
Note before connecting the device
Note
The varying voltage power supply module is designed for operation on 120/230/240 V AC
networks. The setting of the voltage range takes place automatically.
WARNING
Do not connect or disconnect power and data cables during thunderstorms.
WARNING
The device is designed for operation on grounded power supply networks (TN networks to
VDE 0100, Part 300, or IEC 60364-3).
Operation on ungrounded or impedance-grounded power networks (IT networks) is
prohibited.
WARNING
The permitted nominal voltage of the device must conform with local mains voltage.
CAUTION
The mains connector must be disconnected to fully isolate the device from mains. Ensure
easy access to this area.
A master mains disconnect switch must be installed if the device is mounted in a switch
cabinet.
Always ensure free and easy access to the power inlet on the device or that the safety
power outlet of the building installation is freely accessible and located close to the device.
Note
The power supply contains an active PFC (Power Factor Correction) circuit to conform to the
EMC guidelines.
Uninterruptible AC power systems (UPS) must supply a sinusoidal output voltage in the
normal and buffered mode when used with SIMATIC PCs with an active PFC.
UPS characteristics are described and classified in the standards EN 50091-3 and IEC
62040-3. Devices with sinusoidal output voltage in the normal and buffered mode are
identified with the classification "VFI-SS-...." or "VI-SS-....".