User manual

1-4
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
Connections
PROFIBUS-DP
ASi cable
24 V DC power supply
Optical isolation between PROFIBUS-DP and ASi
Direct ET 200 Handheld connection possible for setting the station num-
ber (using an adapter cable)
ASi diagnostics using LEDs
The diagnosis can also be read using the DP master.
The DP/ASi link has LEDs with the following meanings
RUN
BF (bus error)
ASi POWER FAIL (ASi power supply failure)
CONFIG ERROR (configuration error)
AUTOPROG AV (automatic programming possible)
CONFIG MODE (configuration mode)
ASi-SLAVE FAIL (5 LEDs for displaying the failed ASi slave)
The DP/ASi link can be operated on the PROFIBUS-DP with a baud rate
of up to 12000 kBd.
Length of PROFIBUS bus cable
The following values apply to installation of the DP/ASi link for the
PROFIBUS bus cable as a function of the baud rate on the bus.
Table 1-1 Length of the PROFIBUS bus cable as a function of the baud rate on the
PROFIBUS DP bus
Baud Rate Max. Length of Bus Cable
< 187.5 kBd 1200 m per segment
187.5 kBd 1000 m per segment
500 kBd 400 m per segment
1500 kBd 200 m per segment
> 1500 kBd 100 m per segment
Overview