User manual
C-11
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
Bytes 16 to 31 reflect the setpoint configuration of the DP/ASi link. An ASi
slave is permanently assigned to every nibble. If an ASi slave has been confi-
gured, its hexadecimal I/O code has to be entered at this stage; unconfigured
ASi slaves have to be identified by F
H
.
Table C-11 I/O code of configured ASi slaves
Byte
Bits 7 to 4 Bits 3 to 0
16 Not applicable I/O code for slave 1
17 I/O code for slave 2 I/O code for slave 3
18 I/O code for slave 4 I/O code for slave 5
19 I/O code for slave 6 I/O code for slave 7
20 I/O code for slave 8 I/O code for slave 9
21 I/O code for slave 10 I/O code for slave 11
22 I/O code for slave 12 I/O code for slave 13
23 I/O code for slave 14 I/O code for slave 15
24 I/O code for slave 16 I/O code for slave 17
25 I/O code for slave 18 I/O code for slave 19
26 I/O code for slave 20 I/O code for slave 21
27 I/O code for slave 22 I/O code for slave 23
28 I/O code for slave 24 I/O code for slave 25
29 I/O code for slave 26 I/O code for slave 27
30 I/O code for slave 28 I/O code for slave 29
31 I/O code for slave 30 I/O code for slave 31
Setpoint
configuration
Parameterization Message