Technical data

AS-Interface (AS-i)
1-10
SIMATIC NET AS-Interface Introduction and Basic Information
C79000-G8976-C089/03
space of approximately 2 cm
3
.
S Increased functionality, more uses for the customer
Direct integration allows devices to be equipped with a wide range of functions.
Four data and four parameter lines are available. The resulting intelligent
actuators/sensors increase the possibilities, for example, monitoring, parameter
assignment, wear or pollution checks etc.
S Additional power supply for higher power requirements
An external source of power can be provided for slaves with a higher power
requirement (see /1/).
System Limits
S Cycle time
max. 5 ms with standard AS-i slaves
max. 10 ms with AS-i slaves using the extended addressing mode
AS-i uses constant message lengths. Complicated procedures for controlling
transmission and identifying message lengths or data formats are not
required. This makes it possible for a master to poll all connected standard
slaves within a maximum of 5 ms and to update the data both on the master
and slave.
If only one AS-i slave using the extended addressing mode is located at an
address, this slave is polled at least every 5 ms. If two extended slaves (A
and B slave) share an address, the maximum polling cycle is 10 ms. (B
slaves can only be connected to extended masters.)
S Number of connectable AS-i slaves
Maximum of 31 standard slaves
Maximum of 62 slaves with the extended addressing mode
AS-i slaves are the input and output channels of AS-i system. They are only
active when called by the AS-i master. They trigger actions or transmit
reactions to the master when commanded.
Each AS-i slave is identified by its own address (1 to 31). A maximum of 62
slaves using the extended addressing mode can be connected to an
extended master. Pairs of slaves using the extended addressing mode
occupy one address; in other words, the addresses 1 to 31 can be assigned
to two extended slaves.
If standard slaves are connected to an extended master, these occupy a
complete address; in other words, a maximum of up to 31 standard slaves
can be connected to an extended master.
S Number of inputs/outputs
A maximum of 248 binary inputs and outputs with standard modules
A maximum of 248 inputs/186 outputs with modules using the
extended addressing mode
Each standard AS-i slave can receive 4 bits of data and send 4 bits of data.