Specifications
PROFIBUS
System Overview
Topologies
2/77
Siemens LV 1 · 2007
2
Optical network
The optical conductor variant of PROFIBUS has the following
features:
• Transmission path is insensitive to electromagnetic interfer-
ence
• Suitable for long ranges
• Electrical isolation
• Uses either plastic or PCF or glass optical conductors
Optical PROFIBUS with OLMs
Using optical link modules (OLMs) it is possible to configure an
optical network as a line, ring or star structure. The maximum
distance between two OLMs can be 15 km. The transmission
rate is adjustable in steps from 9.6 kbit/s to 12 Mbit/s.
Optical PROFIBUS with integrated interface and OBT
The optical PROFIBUS with integrated interface and OBT is con-
figured as a line structure. A cost-optimized solution in the form
of devices with an integrated optical interface is available for this
purpose. Terminal equipment with an RS 485 interface can be
connected through an optical bus terminal (OBT). The maximum
distance between two stations on a plastic optical conductor is
50 m. Special optical conductors are used to span distances of
up to 300 m.
Network configuration of the optical PROFIBUS with OLMs
G_IK10_XX_50136
S7-300
with CP 342-5
ET 200pro
S7-400
with CP 443-5
Drive
OLM OLM OLM OLMOLM
PC
with CP 5613 A2
Bus cable
for PROFIBUS
Glass FO cable
© Siemens AG 2007