Specifications

AS-Interface
Slaves
Special integrated solutions
AS-Interface communications modules
2/48
Siemens LV 1 · 2007
2
3RK1 400-1CD00-0AA2
AS-Interface communications module for printed circuit
board installation
1)
Note: Pad numbering, see section Dimensional Drawings in the LV1 T
"Technical Information".
With the 4I/4O module for printed circuit board mounting it is
possible for up to four mechanical contacts or 3-wire sensors
according to IEC 947-5-2 to be connected or indicator lights to
be operated, the power for the short-circuit resistant solid-state
switching outputs being provided from an auxiliary voltage
(24 V PELV).
Mounting is very easy using a "Card Edge Board-to-Board-
Connector". This connector can be ordered for vertical and hor-
izontal mounting from the company AMP, for example:
180° version for vertical mounting (AMP):
Order number 530843-2
90° version for horizontal mounting (AMP):
Order number 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
3RK1 200-0CD00-0AA2
AS-Interface communications module for printed circuit
board installation
1)
Note: Pad numbering, see section Dimensional Drawings in the LV1 T
"Technical Information".
With the 4I module for printed circuit board mounting it is possi-
ble for up to four mechanical contacts or 3-wire sensors to be
connected, the power for inputs being provided from AS-Inter-
face cable.
Mounting is very easy using a "Card Edge Board-to-Board-
Connector". This connector can be ordered for vertical and hor-
izontal mounting from the company AMP, for example:
180° version for vertical mounting (AMP):
Order No. 530843-2
90° version for horizontal mounting (AMP):
Order No. 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
Selection and ordering data
Connection Connection pad
1)
ASi+
27, 29
ASi-
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
U
aux
+ (L24+) 2, 4
U
aux
- (M24) 1, 3
OUT1
9
OUT2
10
OUT3
5
OUT4
6
OUT-
7, 8
Not assigned
11, 12, 25, 26
Connection Connection pad
1)
ASi+
27, 29
ASi-
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
Not assigned
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 25, 26
Version DT Order No. Price
per PU
PU
(UNIT,
SET, M)
PS* PG Weight
per PU
approx.
kg
3RK1 400-0CD00-0AA3
3RG9 005-0SA00
4 inputs / 4 outputs
• Supply of I/Os using AS-Interface cable
(max. 200 mA)
Printed circuit board with solder pins, protected
by enclosure
}
3RK1 400-0CD00-0AA3 1 1 unit 121 0.042
• Supply of I/Os using external auxiliary voltage
(24 V PELV)
- Printed circuit board with solder pins,
protected by enclosure
D 3RK1 400-0CD01-0AA3 1 1 unit 121 0.040
- Printed circuit board with solder pins
for horizontal mounting
C
3RG9 005-0SA00 1 1 unit 121 0.025
• Supply of outputs using external auxiliary
voltage (24 V PELV)
Printed circuit board with gold-plated direct
connector for 30-pole male connector socket
for simple installation with direct connector
B
3RK1 400-1CD00-0AA2 1 1 unit 121 0.028
4 inputs
• Printed circuit board with gold-plated direct
connector for 30-pole male connector socket
• For simple installation with direct connector
C
3RK1 200-0CD00-0AA2 1 1 unit 121 0.025
* You can order this quantity or a multiple thereof.
© Siemens AG 2007