Specifications

AS-Interface
ASIsafe
AS-Interface safety monitors
2/14
Siemens LV 1 · 2007
2
Overview
The safety monitor is the centerpiece of ASIsafe. A safe applica-
tion is configured using a PC and the safety monitor. Various ap-
plication-specific operating modes can be selected for this.
They include, for example, an EMERGENCY-STOP function,
tumbler and selection of stop Category 0 or Category 1.
To be able to make full use of the AS-Interface diagnostics op-
tions, the monitor can also be operated with an AS-Interface ad-
dress if required. With the help of the diagnostics block for
STEP7, which is included on the ASIsafe CD, the full diagnostics
spectrum can be processed further in the higher-level PLC.
The monitor comes in two expansion levels:
Basic safety monitor with starter set of modules and basic
functionality
Expanded safety monitor with expanded features and func-
tionality
Both expansion levels are available with one or two enabling cir-
cuits with two-channel configuration.
The safety monitor is used in an AS-Interface bus system to mon-
itor protective devices, e.g. EMERGENCY-STOP switches. It is
classified in Safety Category 4 according to EN 954-1.
According to IEC 61508 the safety monitor can be used in loops
up to SIL3. The user must calculate the PFD value of the total
loop.
Note: Depending on the choice of safety components used, the
complete safety system may also be classified in a lower safety
category.
Selection and ordering data
ON period
in months
Total operating
time in years
PFD
3 10 4 × 10
-5
6 10 6 × 10
-5
9 10 9 × 10
-5
Version DT Order No. Price
per PU
PU
(UNIT,
SET, M)
PS* PG Weight
per PU
approx.
kg
3RK1 105-1BE04-0CA0
Basic safety monitors
• One enabling circuit } 3RK1 105-1AE04-0CA0 1 1 unit 121 0.336
• Two enabling circuits }
3RK1 105-1BE04-0CA0 1 1 unit 121 0.408
Expanded safety monitors
• One enabling circuit A 3RK1105-1AE04-2CA0 1 1 unit 121 0.336
• Two enabling circuits A
3RK1105-1BE04-2CA0 1 1 unit 121 0.408
ASIsafe CD }
3RK1 802-2FB06-0GA0 1 1 unit 121 0.212
• Configurations software asimon V2
• Diagnostics package for STEP7 (FB102)
3RK1 901-5AA00
Cable sets }
3RK1 901-5AA00 1 1 unit 121 0.054
• PC configuration cable
• Transfer cable
Sealable covers } 3RP1 902 1 5 units 101 0.004
* You can order this quantity or a multiple thereof.
© Siemens AG 2007