Specifications

AS-Interface Master
Master for SIMATIC S7
CP 243-2
6/75
Siemens IK PI · 2009
6
Overview
The CP 243-2 is the AS-Interface master for the innovated
generation of SIMATIC S7-200. The communications processor
(6GK1 243-2AX01-0AX0) supports the extended AS-Interface
specification V2.1 and has the following functions:
Up to 62 AS-Interface slaves can be connected and inte-
grated analog value transfer (according to the extended
AS-Interface specification V2.1)
Supports all AS-Interface master functions in accordance with
the extended AS-Interface specification V2.1
Status displays for operating states and display of the func-
tional readiness of connected slaves with LEDs in the front
panel
Indication of errors (incl. AS-Interface voltage errors,
configuration errors) with LEDs in the front panel
Compact enclosure designed to match the new generation of
SIMATIC S7-200.
Benefits
More flexible and extended application options of the
SIMATIC S7-200 due to the considerable increase in the
available digital and analog inputs/outputs
Shorter startup times due to easy configuration at the press of
a button
In the event of a fault, shorter standstill and service times due
to LED indication of:
Status of the CPs
- connected slaves and their operational readiness
- monitoring of the AS-Interface voltage level
Application
The CP 243-2 is the AS-Interface master connection exclusively
for the CPUs 22x of the innovated SIMATIC S7-200 generation.
By connecting to AS-Interface, the available digital inputs and
outputs for S7-200 are significantly increased (max. 248 DI /
186 DO on AS-Interface per CP).
In addition, the integrated analog value processing also makes
analog values (per CP max. 31 analog slaves, each with up to
4 channels) available to the S7-200 at the AS-Interface. Up to
two CP 243-2s can be operated simultaneously on the S7-200.
Design
The CP 243-2 is connected to the S7-200 like an expansion
module. It features:
Two terminals for direct connection of the AS-Interface cable
LEDs in the front panel for displaying the operating status and
the operational readiness of all connected and activated
slaves
Two pushbuttons for displaying the status information of the
slaves, for switching the operating status and entering the ex-
isting ACTUAL configuration as the SETPOINT configuration
Function
The CP 243-2 supports all of the specified functions of the ex-
panded AS-Interface specification V2.1. This makes it possible
to operate up to 62 digital slaves or 31 analog slaves on the
AS-Interface by means of duplicate address assignment (A-B).
Access to the analog values is just as easy as accessing the
digital values thanks to the integrated analog value processing.
In the process image of the S7-200, the CP 243-2 occupies a
digital input byte (status byte), a digital output byte (control
byte), 8 analog input words and 8 analog output words. This
means that the CP 243-2 occupies two (logical) slots. Using the
status byte and the control byte, the mode of the 243-2 can be
set in the user program.
Depending on the mode, the CP 243-2 saves either the digital or
analog I/O data of the AS-Interface slaves or diagnostic values
in the analog address space of the S7-200 or allows the master
calls (e.g. changes to the slave addresses).
Configuration
All of the connected AS-Interface slaves are configured by
the press of a button. No further configuration of the CP is
necessary.