Specifications

AS-Interface
System components and accessories
Repeater/extender
6/149
Siemens IK PI · 2009
6
Design
Repeater
Slaves can be used on both sides of the repeater
AS-Interface power supply required on both sides
Galvanic isolation of the two AS-Interface shaped cable lines
Installed in K45 module case with mounting plate
Separate indication of the correct AS-Interface voltage for
each side
No more than two repeaters can be used in series
(max. cable length 300 m)
Parallel connection of several repeaters is possible
(point-to-point configuration)
Combination of series and parallel switching is possible
(max. extent 500 m)
Connection of repeaters
Extender
Master can be positioned up to 100 m from actual AS-Inter-
face segment.
Slaves can only be used on the opposite side to the master.
An AS-Interface power supply is required only on the side
opposite to the master.
No galvanic isolation of the two AS-Interface shaped cable
lines.
Indication of the correct AS-Interface voltage.
Installed in user module case with FK-E coupling module as
lower part.
Extender connection
Note:
The extender can not be operated with the
DP/AS-Interface link 20E.
Ordering data Order No.
3RZHU
VXSSO\
3RZHUVXSSO\
3RZHUVXSSO\
3RZHU
VXSSO\
5HSHDWHU
5HSHDWHU 5HSHDWHU
6
6666
6
$6,QWHUIDFH
P P P
0
*B,.B;;B
3RZHUVXSSO\ 3RZHUVXSSO\
([WHQGHU
1RVODYHV
5HSHDWHU
666
$6,QWHUIDFH
P P P
0
*B,.B;;B
Repeater für AS-Interface 6GK1 210-0SA01
for cable extension including
mounting plate
Extender for AS-Interface 6GK1 210-1SA00
for remote mounting of the master
including coupling module FK-E