Specifications

AS-Interface Slaves
Special integrated solutions
AS-Interface communication modules
6/106
Siemens IK PI · 2009
6
Overview (continued)
3RK1 400-1CD00-0AA2, 3RK2 400-1FD00-0AA2 AS-Interface
communication module for printed-circuit board installation
1)
Note: Pad numbering, see section Dimensional Drawings in Catalog LV1 T
"Technical Information".
With the 4E/4A or 4E/3A module for printed-circuit board
mounting it is possible for up to four mechanical contacts or
3-conductor sensors according to IEC 947-5-2 to be connected.
Up to four indicator lights via the 4E/4A module or up to three
indicator lights via the 4E/3A module can also be controlled. The
power for short-circuit resistant solid-state switching outputs is
provided from an auxiliary voltage (24 V PELV).
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
180° version for vertical mounting (AMP):
Order No. 530843-2
90° version for horizontal mounting (AMP):
Order No. 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
3RK1 200-0CD00-0AA2 AS-Interface communication module
for printed-circuit board installation
1)
Note: Pad numbering, see section Dimensional Drawings in Catalog LV1 T
"Technical Information".
With the 4I module for printed-circuit board mounting it is
possible for up to four mechanical contacts or 3-conductor
sensors to be connected, the power for inputs being provided
from AS-Interface cable.
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
180° version for vertical mounting (AMP):
Order No. 530843-2
90° version for horizontal mounting (AMP):
Order No. 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
Connection Connection pad
1)
AS-i + 27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
U
aux
+ (L24+) 2, 4
U
aux
- (M24) 1, 3
OUT1
9
OUT2
10
OUT3
5
OUT4
6 (not assigned for 4E/3A module
3RK2 400-1FD00-0AA2)
OUT-
7, 8
Not assigned
11, 12, 25, 26
Connection Connection pad
1)
AS-i + 27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
Not assigned
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 25, 26