Programming FCs (Functions) and FBs for S7 Ethernet CPs
158
SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06
Table 5-2 AG_SEND / AG_LSEND Codes
DONE MeaningSTATUSERROR
0 1 8F7FH Internal error, e.g. illegal ANY reference.
e.g. parameter LEN=0
0 1 8090H No module with this address exists or the CPU is in the STOP
mode.
0 1 8091H Logical base address not at a double word boundary.
0 1 8092H In the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A4H The communication bus connection between the CPU and CP is
not established. (Only with newer CPU versions)
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The specified length (in the LEN parameter) is incorrect.
0 1 80B2H The communication bus connection between the CPU and CP is
not established.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H CPU resources (memory) occupied.
0 1 80C4H Communication error (occurs temporarily and a repetition in the
user program will often remedy the problem).
0 1 80D2H Module base address incorrect.