Data Sheet for Product
2/4
Siemens Building Technologies DESIGO RX connection to SICLIMAT X CK1N9816en
Landis & Staefa Division 05.12.2000
Configuration
PRU2
1
PROFIBUS-FMS
Terminal bus TCP/IP
X-OS
X-BS
CP5412-A2
DESIGO RX
PRU2 PRU2
26
Performance criteria
The connection of the RX controllers via LON bus is an integral part of the PRU2
version 7. The data storage of RX objects and the communication procedure via
PROFIBUS FMS is specified by the configuration of the PRU2 Version 7 and cannot be
altered.
The connection of the PRU2 is provided by a new PCCRX communication driver in the
SICLIMAT X OS.
It is possible to connect up to 26 PRU2 to one SICLIMAT X OS.
Currently only one bus line of PRU2s are supported by SICLIMAT X OS.
The following SICLIMAT X functions are available:
− Operating/monitoring of images incl. Nobis
− Central time switching (local time switching not possible)
− Tecla
− Type-specific protocols (e.g. state protocols)
− Trend
− Archiving of process data
Engineering
The complete engineering of the PRU2 is contained in two files, one *.hlk file and one
*.adr file.
These files are loaded with a SICLIMAT tool (Rxdli). All relevant information is
evaluated and filed (DLI file) in the format specified for the SICLIMAT X data import.
The data import function is used to transmit the RX data to the SICLIMAT X OS via the
engineering manager.
The RX objects (room, light, blinds) are an integral part of the SICLIMAT X object
database and can, therefore, be fully mapped.