Siemens Building Technologies PROFIBUS DP/P-bus link
Building Automation User's guide 1-3
1.4 Features
On the P-bus side, the DP/P-bus link is enabled for the local bus (a P-bus cable up to 50m in
length). On the Profibus side, distances of up to 1000m can be covered.
The number of DESIGO I/O modules per DP/P-bus link depends on the following conditions:
Maximum 50 DESIGO I/O modules are supported
Up to 128 load units
Max. 216 input bytes
Max. 216 output bytes
The maximum total must not exceed 216 bytes
Programmable Profibus DP address spaces 1…99
The following example shows how to determine the number of load units and address space:
With the module mix shown in the table below, the totals are 9 load units and an address space
of 6 input bytes and 9 output bytes. For the maximum configuration, a further 119 load units and
an additional 201 input/output bytes are available for the I/O modules.
DESIGO
I/O modules
Load units Input bytes Output
bytes
PTM1.2D20 DIGITAL INPUT 2 x DI
potential-free contacts DC 22 V
2 1 0
PTM1.4QD DIGITAL OUTPUT 2 x DO;
with feedback
4 1 1
PTM1.2P100 ANALOG INPUT 2 x AI; 0…250 ohms
Pt100/Ni100 (4-wire)
2 4 0
PTM1.4Y10S ANALOG OUTPUT 4 x AO
0…10V
1 0 8
Total 9 6 9