User Manual
PROFIBUS DP/P-bus link Siemens Building Technologies
4-6 User's guide Building Automation
SIMATIC S7 PTM1.2P100
Decimal Hex. Ohms
L&S Ni1000
standard range in °C
(1 digit = 0.1 K)
Range
32767 7FFF >408.1
3874 F22 408.1
Overflow, error
3873 F21 250 408
600 258 123.24 60
0 0 100 0
-2582 F5EA 0 -234
Nominal range
-2581 F5EB -233.9
-32768 8000 <-233.9
Overflow, error
Tab. 4-4: Pt100 measuring ranges
SIMATIC S7 PTM1.2P1K
Decimal Hex. Ohms
L&S Pt1000
standard range in °C
(1 digit = 0.1 K)
Range
32767 7FFF >408.1
3874 F22 408.1
Overflow, error
3873 F21 2500 408
600 258 1232.4 60
0 0 1000 0
-2582 F5EA 0 -234
Nominal range
-2581 F5EB -233.9
-32768 8000 <-233.9
Overflow, error
Tab. 4-5: Pt1000 measuring ranges