User Manual
PROFIBUS DP/P-bus link Siemens Building Technologies
3-2 User's guide Building Automation
3.1.1 Station status 1
Bit Description Cause / Remedy
0
1: No access to the DP/P-bus link
from the master
Is the Profibus address set correctly?
Is the bus plug connected?
Voltage to the DP/P-bus link ok?
DP/P-bus link reset carried out?
1
1: The DP/P-bus link is not ready to
exchange data
Wait until start-up procedure is complete
2 1: The engineering data transmitted by
the master to the DP/P-bus link does
not correspond to the actual structure
Correct station type or correct DP/P-bus link
structure entered in the engineering soft-
ware?
3 1: External diagnosis available
(common diagnostic display)
Evaluate diagnosis. The bit will be reset as
soon as all errors have been cleared.
4 1: The DP/P-bus link does not support
the required function (e.g. modifica-
tion of Profibus address via the soft-
ware)
Check engineering procedure.
5 1: The master cannot interpret the re-
sponse from the DP/P-bus link.
Check the bus structure.
6 1: The DP slave type does not match
the software engineering
Enter the correct station type in the engineer-
ing software.
7 1: The DP/P-bus link parameters were
set by another DP master.
The bit is always set to 1 whenever a pro-
gramming device, for example, or another
DP master accesses the DP/P-bus link.
The Profibus address of the DP master which
set the DP/P-bus link parameters, in the
“Master Profibus address” diagnostic byte.