Data Sheet for Product
CK1N9850en
17.08.2001
Siemens Building Technologies
Building Automation
9
850
SICLIMAT™ X
SICLIMAT X
Maximum demand control
ZLXHLO
This maximum demand control software saves energy costs for the building
services operator by ensuring that the energy-consumption level never exceeds
the limit defined by the tariff.
Use
Utilities companies do not only bill major energy users for the amount of energy
consumed (kilowatt-hour rate), but also charge a rate based on peak demand. For
major users, the unit price is determined primarily by the power actually consumed. By
limiting maximum demand to a contractually agreed level, the user can avoid excess
charges and reduce power consumption.
The EMAX module in SICLIMAT X ensures that energy consumption does not exceed
the maximum demand level defined by the tariff. It does this by monitoring energy
consumption at regular intervals over a given measurement period, and extrapolating
the demand to the end of the measurement period.
If the extrapolation indicates that the tariff limit will be exceeded, the maximum demand
program will shed some of the electrical loads under its control.
However, as soon as an energy reserve is predicted, the disabled electrical loads will
be re-enabled.
The EMAX module can also handle generators (e.g. emergency generators) in a similar
way.