Data Sheet for Product

Features
Supports OPC DA 2.05 (data access)
Supports the following types of access: Subscribe/unsubscribe OPC items (no
polling);
read/write single OPC items – read from cache/device
Supports the following objects: VT_Bool, VT_I1, VT_I2, VT_I4, VT_UI1,VT_UI2,
VT_UI4, VT_R4, VT_R8, VT_Array
INVERS For inversion of a Boolean function
NORMAL Cancels an existing INVERS operation.
ABS Generates the absolute value
BIAS val Shifts the value received by the amount defined by
the transmitted parameter
BIT start len Cuts out a bit-field from the transmitted value
BITPOS start len From the value received, cuts out and right-justifies a bit field
of length len, starting from "BIT start".
KEHRWERT Generates the reciprocal value
SWAP mode Swaps individual bytes in the word received
KH u_sicx o_sicx l_ag h_ag
is the classic characteristic for the units of measurement
in SIMATIC S5. u_sicx and o_sicx are the high and low limits
of the associated final value.
Data points integrated via OPC can be processed in the system in the same way as
normal SICLIMAT X data points.
o Display
o Alarms
o Reporting
o TECLA centralized event switching
o Centralized time switching
o Archiving
o Trend logging
New, simple SICLIMAT X objects (NOBIs), equivalent to the simple OPC Items, are
supplied with OPC Client
o OPC-DIG2, OPC-DIG2 RO Boolean operation
o OPC-DIG2, OPC-DIG2 RO 4-bit variable
o OPC-DIG16, OPC-DIG16 RO 16-bit variable
o OPC-Float, OPC-Float RO Analog variable
o OPC-UNIT OPC integer
Positive numbers only
o OPC-INT OPC integer, full numerical range
And simple compound blocks (NOBIs)
o OPC-SB01, 03, 15 OPC switching command
o OPC-Soll Simple OPC setpoint/position command
o OPC-Mess Simple OPC measured value with one
pair of limit values
2/4
Siemens Building Technologies OPC Client for SICLIMAT X CK1N9888en
Building Automation 11.01.2005