Building Technologies 049_Archives_and_Libraries_A6
V10271399_a_en.doc
Fire Safety & Security Products 03.2009
6.1.2 Fire Safety
6.1.2.1 BS / EN
No Description Document
1 Number of smoke detectors
BS6266 annex A
2 Additional Smoke (Aspirating smoke detection)
BFPSA Cat 1 / EN54-20
3 Additional hand portable extinguishers
BS 5306-8
4 Fixed gaseous extinguishing systems
BS 5306-0 & ISO14520
5 Existing Sprinkler Systems within the room
BS 5306-2
6 Foam systems (Certain Floor Voids)
BS 5306-6.2
7 Types of extinguishing for categories a, b, c, d, e,
BS 6266 annex B
8 Cables in risk “cat d & e” not meeting BS EN 50289-4-11
BS 6266-6.4
9 Full Risk Assessments for such applications should be
made in conjunction with other regulations applicable e.g.:-
Building materials and structures
BS476
Tab. 18 BS / EN Norms for archive and library
Classification for aspirating smoke detection EN54-20
Class Description Example application(s)
A
Aspirating smoke
detector providing very
high sensitivity
Very early detection:
The detection of very dilute smoke for example entering air
conditioning ducts to detect the extremely dilute concentrations
of smoke that might emanate from equipment in the environment
controllers area such as a clear room.
B
Aspirating smoke
detector providing
enhanced sensitivity
Early detection:
For example special fire detection or close to particulary valu-
able, vulnerable or critical items such as computer or electronic
equipment cabinets
C
Aspirating smoke
detector providing
normal sensitivity
Standard detection:
General fire detection in normal rooms or spaces, giving, for
example, at least an equivalent level of detection as a point or
beam type smoke detection system
Tab. 19 Classification table EN54-20
6.1.2.2 VdS
No Description Document
1 Guidelines for automatic fire detection and fire alarm sys-
tems
VdS 2095, Annex B, C
2 Triggering of extinguishing systems
VdS 2496
3 Fire extinguishing systems using non liquefied inert gases
VdS 2380
4 Fire extinguishing systems using halocarbon gases
VdS 2381
5 Guidelines for CO
2
fire extinguishing system, Planning and
installation
VdS 2093 (2006-09)
Tab. 20 VdS Norms for archive and library