User Manual
Fire Safety
56
Building Technologies 049_Archives_and_Libraries_A6
V10271399_a_en.doc
Fire Safety & Security Products 03.2009
Pressure relief venting through another enclosure
Suppose there isn't an outside wall. Following topics should be taken into account:
– Is this an escape route (inc Fire Officer / Building Control)
– Cascade of pressure – escalating the problem
– False alarms elsewhere from entrained smoke
Suppose there isn't an outside
wall, venting into an adjacent
room (without pressure relief
vent) maybe acceptable if
venting through a warehouse
with a volume at least 70%
bigger.
Fig. 30 Pressure venting
Suppose there isn't an outside wall, venting into an adjacent room (without pres-
sure relief vent) maybe acceptable if venting through a warehouse with a volume
at least 70% bigger.
Suppose there isn’t an outside
wall, venting into an adjacent
room (with a pressure relief
vent) is possible, but cascade
pressure should be considered
(to open the flap and overall
pressure differential)
Fig. 31 Pressure venting
Chemical agents exert a small initial positive pressure,
– followed by a larger negative pressure,
– followed by a positive pressure of similar magnitude.
Fig. 32 Negative pressure “Gulp”
Negative pressure “gulp” The enclosure needs to withstand the negative pressure
phase, and dynamic of this.
Pressure relief venting in chemical agents can be engineered as pressure relief
flap pneumatically operated from the pressure within the discharge pipework, as
gravity flaps (preferred and most used option) or as electrically operated (rarely
used and not recommended).
Flo
w
Direction
Room A
Room must be 70%
Bigger than room A
Flow
Direction
Room A