User Manual

Fire Safety
48
Building Technologies 049_Archives_and_Libraries_A6
V10271399_a_en.doc
Fire Safety & Security Products 03.2009
to an optimum level, so that the gas flow and the water flow can be converged be-
hind the gas orifice.
Fig. 19 Sinorix
TM
H
2
O system
Sinorix
TM
H
2
O Gas has the following advantages:
Fast and efficient extinguishing due to the oxygen depletion combined with cool-
ing effect
Reliably avoids re-ignition, typical in deep seated fires
Excellent property protection due to minimal water use: Droplet spectrum and
water fog can be designed for an optimum cooling effect
Cost savings through shared piping network and nozzles for water and nitrogen
Increased safety for people through the reduction of toxic fumes
Precisely tailored to customer needs thanks to special system design software
Sinorix H
2
O Gas extinguishing solution
Extinguishing agents Nitrogen (N
2
) and water (H
2
O)
Tank pressure (N
2
) 200 bar or 300 bar
Nozzle pressure 10 – 60 bar
Nozzle openings 3 – 23 mm
Droplet speed 50 – 150 m/s
Droplet size 10 – 50 µm
Coverage from each nozzle 30 m
2
Piping network
Galvanized steel pipes, designed for 60 bar
operating pressure
Amount of water 0.3 – 1.0 kg/m
3
(according to risk of fire)
Application Class A, B and C fires
Flooding time 60 – 120 s
Approval VdS (S37002)
Tab. 8 Sinorix
TM
H
2
O gas extinguishing solution
Additional key aspect, especially when protecting old buildings and historic build-
ings is that Sinorix
TM
H
2
O Gas requires smaller overpressure flap openings. As part
of the nitrogen is used to propel the water, there is a resulting softened initial burst
of gas, which turns into less required overpressure openings and thus lower costs.