User Manual
Fire Safety
48
Building Technologies 049_Archives_and_Libraries_A6
V10271399_a_en.doc
Fire Safety & Security Products 03.2009
to an optimum level, so that the gas flow and the water flow can be converged be-
hind the gas orifice.
Fig. 19 Sinorix
TM
H
2
O system
Sinorix
TM
H
2
O Gas has the following advantages:
– Fast and efficient extinguishing due to the oxygen depletion combined with cool-
ing effect
– Reliably avoids re-ignition, typical in deep seated fires
– Excellent property protection due to minimal water use: Droplet spectrum and
water fog can be designed for an optimum cooling effect
– Cost savings through shared piping network and nozzles for water and nitrogen
– Increased safety for people through the reduction of toxic fumes
– Precisely tailored to customer needs thanks to special system design software
Sinorix H
2
O Gas extinguishing solution
Extinguishing agents Nitrogen (N
2
) and water (H
2
O)
Tank pressure (N
2
) 200 bar or 300 bar
Nozzle pressure 10 – 60 bar
Nozzle openings 3 – 23 mm
Droplet speed 50 – 150 m/s
Droplet size 10 – 50 µm
Coverage from each nozzle 30 m
2
Piping network
Galvanized steel pipes, designed for 60 bar
operating pressure
Amount of water 0.3 – 1.0 kg/m
3
(according to risk of fire)
Application Class A, B and C fires
Flooding time 60 – 120 s
Approval VdS (S37002)
Tab. 8 Sinorix
TM
H
2
O gas extinguishing solution
Additional key aspect, especially when protecting old buildings and historic build-
ings is that Sinorix
TM
H
2
O Gas requires smaller overpressure flap openings. As part
of the nitrogen is used to propel the water, there is a resulting softened initial burst
of gas, which turns into less required overpressure openings and thus lower costs.