User Guide

Document No.129-335
Installation Instructions
June 22, 2005
VE0268R1
1
2
Figure 2. Mounting the Actuator on a Valve.
The installation is now complete.
Removing the Actuator from a Valve
1. Disconnect the wiring.
2. Unscrew actuator-coupling piece from the valve body
threads.
3. Remove the actuator from the valve.
Wiring
All wiring must conform to NEC and local codes and
regulations.
Use earth ground isolating step-down Class 2
transformers.
NOTE: Do not use autotransformers.
Determine the supply transformer rating by summing
the total VA of all actuators used. The maximum
rating for a Class 2 step-down transformer is 100 VA.
NOTE: It is recommended that one transformer power
no more than 10 actuators.
SFA71U/SFP71U 24 Vac actuators: Wiring
connection can be made inside the actuator housing
(remove the housing top for access).
Line voltage actuators: Wiring connection requires
junction box and flex conduit no further than
15 inches (381 mm) from actuator.
G
G0
(Red)
(Black)
24 Vac
Neutral
EA0993R2
CAUTION:
G0 and G must be properly wired for correct
function and full life of the actuator.
Figure 3. 24 Vac Actuator Wiring Diagram.
L
N
(Black)
(White)
120 Vac
Neutral
(Green)
GND
EA1036R2
Figure 4. 120 Vac Actuator Wiring Diagram.
L
N
(Red)
(White)
208 Vac
208 Vac
(Green)
GND
EA1140R1
Figure 5. 208 Vac Actuator Wiring Diagram.
L
N
Neutral
(Blue)
(White)
277 Vac
(Green)
GND
EA1139R1
Figure 6. 277 Vac Actuator Wiring Diagram.
Page
2 of 4 Siemens Building Technologies, Inc.