Air Conditioner User Manual

Startup Procedures
Siemens Building Technologies, Inc. 35
Parameter Description Action
Setting/
Default
P1211
Number of Restart Attempts
Specifies the number of times
SED2 will attempt to restart after
supply power brownout or fault, if
P1210 automatic restart is
activated.
1. Press
to enter the SED2
parameter mode and to display
r0000.
2. Press
to advance to
parameter P1211.
3. Press
to access the
parameter values level.
4. Press to advance to
desired value.
5. Press
to confirm and save
the setting.
Minimum = 0
Default = 3
Maximum = 10
Suggested =
10
P1212
Time to First Restart
Selects the time (seconds)
before the SED2 is restarted for
the first time if P1210 automatic
restart is activated.
1. Press to enter the SED2
parameter mode and to display
r0000.
2. Press
to advance to
parameter P1212.
3. Press
to access the
parameter values level.
4. Press
to advance to
desired value.
5. Press
to confirm and save
the setting.
Minimum = 0
Default = 3
Maximum = 10
Suggested =
10