Air Conditioner User Manual
SED2 VFD Electronic Bypass Option Operating Instructions
24 Siemens Building Technologies, Inc.
Parameter Description Action
Setting/
Default
P0305*
Rated Motor Current
0A to 10,000A.
Rated motor current (A) from
motor nameplate.
1. Press
to advance to
parameter P0305.
2. Press
to access the
parameter values level.
3. Press
to advance to
nominal current.
4. Press
to confirm and save
the setting.
Setting =
Motor
nameplate
Default =
Varies by
model
P0307*
Rated Motor Power
0 kW or hp to 200 kW or hp.
Rated motor power (kW or hp)
from motor nameplate.
If P0100 =1 (60 Hz, hp, North
America), then motor power is in
hp.
1. Press
to advance to
parameter P0307.
2. Press
to access the
parameter values level.
3. Press to advance to
nominal power.
4. Press
to confirm and save
the setting.
Setting =
Motor
nameplate
Default =
Varies by
model
(hp/voltage
dependent)
P0308*, or
P0309
Rated Motor cosPhi (P308), or
Rated Motor Efficiency (P0309)
0.000 to 1.00 (P0308) or 0.0 to
99.9 (P0309)
Rated motor cosPhi or motor
efficiency from motor nameplate.
If P0100 = 2 and P0307 = kW,
P0308 displays.
If P0100 = 1 and P0307 = hp,
P0309 displays.
P0309 = 100% corresponds to
super conducting.
NOTE:
This parameter is available when
P0003 = 3 and P0010 = 1.
1. Press
to advance to
parameter P0308 or P0309.
2 Press
to access the
parameter values level.
3. Press
to advance to
nominal cosPhi or motor
efficiency.
4. Press
to confirm and save
the setting.
Setting =
Motor
nameplate
P0308 Default
= 0.00
P0309 Default
=
Varies by
model
(hp/voltage
dependent)
* Motor related parameters.