Air Conditioner User Manual

SED2 VFD Electronic Bypass Option Operating Instructions
22 Siemens Building Technologies, Inc.
Parameter Description Action
Setting/
Default
P0003
User Access Level
Allows you to access more
parameters.
1 = Standard
2 = Extended
3 = Expert
1. Press
to access parameter
r0000 and to enter the SED2
parameter mode.
2. Press
to advance to
parameter P0003.
3. Press
to access the
parameter values level.
4. Press
to advance to 3
(expert level).
5. Press
to confirm and save
the P0003 = 3 setting.
Setting = 3
Default = 1
NOTE:
Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available
during quick commissioning.
P0010
Quick Commissioning
0 = Ready to Run
1 = Quick Commissioning
30 = Factory Setting
1. Press to access parameter
r0000 and to enter the SED2
parameter mode.
2. Repeatedly press
to
advance to parameter P0010.
3. Press
to access the
parameter values level.
4. Press
to advance to 1.
5. Press to confirm and save
the P0010 = 1 setting.
Setting = 1
Default = 0
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.