Air Conditioner User Manual

Installation Instructions
Siemens Building Technologies, Inc. 17
Table 3. Wire Sizes and Tightening Torques for E-Bypass with 380V to 480V Drive.
Circuit Breaker
Disconnect
Switch
Overload Ground Lug
Part
Number
Bypass
Frame
Size
HP kW Amps
Wire
Size *
Torque,
lb-in
(Nm)
Wire
Size *
Torque,
lb-in
(Nm)
Wire
Size *
Torque,
lb-in
(Nm)
Range,
Amps
Max
Backup
Fuse,
Amps
Wire
Size*
Torque,
lb-in
(Nm)
VBE30.5---- A 0.5 0.37 1.1
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
.7 - 1.0
4 14-2 35 (4)
VBE30.7---- A 0.7 0.55 1.6
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
1.1 - 1.6
6 14-2 35 (4)
VBE31.0---- A 1.0 0.75 2.1
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
1.4 - 2.0
8 14-2 35 (4)
VBE31.5---- A 1.5 1.1 3.0
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
2.2 - 3.2
12 14-2 35 (4)
VBE32.0---- A 2.0 1.5 3.4
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
2.8 - 4
16 14-2 35 (4)
VBE33.0---- B 3.0 2.2 4.8
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
3.5 - 5
20 14-2 35 (4)
VBE35.0---- B 5.0 4.0 7.6
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(.8 - 1.2)
7 - 10
40 14-2 35 (4)
VBE37.5---- C 7.5 5.5 11
14-10
Cu
32 (3.6) 18-10
13 - 17
(1.5 - 1.7)
18-14
7 - 10.3
(8 - 1.2)
9 - 12
45 14-2 35 (4)
VBE310---- C 10 7.5 14
14-10
Cu
32 (3.6) 18-10
13 to17
(1.5 - 1.7)
14-10
18 - 22
(2 - 2.5)
11 - 16
60 14-2 35 (4)
VBE315---- C 15 11.0 21
14-10
Cu
20 - 60
(2.2 - 6.8)
14-8
17 - 22
(1.9 - 2.5)
14-10
18 - 22
(2 - 2.5)
17 - 22
80 14-2 35 (4)
VBE320---- C 20 15.0 27
10-1/0
Cu
20 - 60
(2.2 - 6.8)
14-8
17 - 22
(1.9 - 2.5)
18-3
27 - 40
(3.1 - 4.5)
22 - 32
125 14-2 35 (4)
VBE325---- D 25 18.5 34
10-1/0
Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
28 - 40
150 14-2 35 (4)
VBE330---- D 30 22.0 40
10-1/0
Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
28 - 40
150 14-2 35 (4)
VBE340---- D 40 30.0 52
10-1/0
Cu
20 - 60
(2.2 - 6.8)
14-6
22 - 27
(2.5 - 3.1)
18-3
27 - 40
(3.1 - 4.5)
40 - 50
200 14-2 35 (4)
VBE350---- E 50 37.0 65
10-1/0
Cu
20 - 60
(2.2 - 6.8)
12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
57 - 75
300 14-2 35 (4)
VBE360---- E 60 45.0 77
3-3/0
Cu
80 (9) 12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
70 - 90
350 14-2 35 (4)
VBE375---- F 75 55.0 96
3-3/0
Cu
80 (9) 12-1
22 - 27
(2.5 - 3.1)
10-1/0
36 - 53
(4.1 - 6)
80 - 100
400 14-2/0 50 (5.6)
VBE3100---- F 100 75.0 124
6 - 350
kcmil
Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
VBE3125---- F 125 90.0 156
6 - 350
kcmil
Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
VBE3125--
HA
F — 90.0 178
6 - 350
kcmil
Cu
120 - 275
(14 - 31.1)
6 - 350
kcmil
120 - 275
(13.5 - 31.1)
6-3/0
124 - 210
(14 - 23.7)
50 - 200 800 14-2/0 50 (5.6)
* Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum
600 Vac.