Siemens Building Technologies SED2 LON Module Operating Instructions CE1B5193en
HVAC Products 4 Startup procedures 26.06.2006
4.2 Verifying parameter operations
After setting VSD parameters, perform the following steps to verify parameter opera-
tions using the drive keypad:
Step Press Action
1
Displays r0000
2
and
Enables scrolling to the appropriate parameter number
3
Displays the value of the selected parameter
4
and
Enables scrolling to the appropriate parameter value
5
Confirms parameter value setting and enables scrolling to
other parameter numbers
6
and then
Returns to the display readout when finished
4.3 Setting up SED2 LON module
To make use of the VSD’s functionality in the building automation and control system,
the Siemens Building Technologies representative is responsible for proper configura-
tion of the VSD for its primary application. This is a prerequisite for commissioning the
LON module.
• Start the VSD by locally setting the keypad parameters per table in section
4.1 Setting Up SED2 parameters.
NOTE: Some parameters may be broken down into index functions. These func-
tions are indicated by the letters “in” within the selected parameter.
For example, for parameter P2041, set [0]
3
to 1 for LON control.
• Install the appropriate file(s) for the network manager tool being used.
NOTES: The device name = Sed2Vfd.
Set the start/stop and speed setpoint via nv2 (nviDrvSpeedStpt).
Use of a Tridium interface
The JAR Script file is already implemented if a Tridium interface of the version
R2.301.428 or higher is used. In case of an older version, please contact:
Siemens Building Technologies Inc. / HVAC Products
Kevin Belles
1000 Deerfield Parkway
60089 Buffalo Grove
USA
E-Mail: kevin.belles@siemens.com
Tel. +1 847 215 1000
3
[0] denotes index and is displayed as “in000“
NOTE: