Installation Instructions

Document No. 129-708
Installation Instructions
May 10, 2016
Siemens Industry, Inc. Page 5 of 6
Figure 8. Final Assembly.
Table 1. Wiring Designations.
Conventional (A)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
108
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
105
8
Digital Input 1
Start Stop
9
24Vdc +
109
6
24 Vdc +
Power 24 Vdc
22
RO1 NO
7
24
RO2 NC
Fault Status
21
RO1 Common
5
25
RO2 Common
Fault Status
Electronic (E)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
Purple
14
Digital Input 4
Run Interlock 1
6
Digital Input 2
Yellow
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
Brown
8
Digital Input 1
Start Stop
28
24 Vdc -
Blue
7
Ground
Power 24 Vdc
25
RO 2 NO
Red
23
RO1 NO
Run Status
24
RO 2 Common
Red
22
RO1 Common
Run Status
22
RO1 NO
Orange
24
RO2 NO
Fault Status
21
RO1 Common
Orange
25
RO2 Common
Fault Status