Table 1. Wiring Designations.
Conventional (A)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
108
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
105
8
Digital Input 1
Start Stop
9
24 Vdc +
109
6
24 Vdc +
Power 24 Vdc
22
RO1 NO
7
24
RO2 NC
Fault Status
21
RO1 Common
5
25
RO2 Common
Fault Status
Electronic (E)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
Purple
14
Digital Input 4
Run Interlock 1
6
Digital Input 2
Yellow
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
Brown
8
Digital Input 1
Start Stop
28
24 Vdc -
Blue
7
Ground
Power 24 Vdc
25
RO 2 NO
Red
23
RO1 NO
Run Status
24
RO 2 Common
Red
22
RO1 Common
Run Status
22
RO1 NO
Orange
24
RO2 NO
Fault Status
21
RO1 Common
Orange
25
RO2 Common
Fault Status
Bypass Parameter Setting
1. Change Ctrl Signal 2 A (3.5.1.2) to a value
of DigIN Slot0.1 (virtual off). This removes
the reverse command from DI2.
2. Change Run Interlock 2 (3.5.1.13) to a
value of DigIN SlotA.2 (use Digital Input 2).
This is used to monitor the M2 Contactor.
3. Change RO2 Function (3.5.3.2.4) to a value
of FaultInvert. This is for fail-safe operation
of fault relay (wired to normally closed
contact). If the inverter loses power but the
bypass does not, then the contact closes to
indicate to the bypass that there is a
problem.
For SED2 Electronic Bypass only when the interlock
feature is enabled, continue to Steps 4 and 5.
4. Change Preset Freq Sel0 (3.5.1.15) to a
value of DigIN Slot0.1 (virtual off) to remove
DI4 from that definition.
5. Change Run Interlock 1 (3.5.1.12) to a
value of DigIN SlotA.4 (use Digital Input 4).
This is used to monitor the terminals 7 and 8
of the SED2 E-Bypass Board.
The installation is now complete. See the SED2 to
BT300 Migration Guide (125-1005) for further
information.