Figure 13. Ground Cable.
7. Remove the crimped ends from all power wiring
and strip 3/8" from the end of each.
8. Terminate existing bypass wiring to the bottom
edge of the terminal block assembly.
Figure 14. Bypass Wiring Termination.
Mounting the BT300 Drive
NOTE: See Installation Instructions DPD01148
(Included with unit) for more complete
instructions.
1. Mount the BT300 to the Drive Adapter Plate
using four 1/4-20 hex nuts with flat washers
(included in the Hardware Kit).
Figure 15. Drive Adapter Plate.
2. Remove cover from the BT300 HVAC Drive.
Figure 16. BT300 HVAC Drive with Cover Removed.
3. Remove the Cable Protection Plate from the
BT300 HVAC Drive.
Figure 17. Cable Protection Plate.
4. Using a knife, slice all three grommets to allow
for wiring to pass through. Install grommets to
the BT300 Drive.