Operating Instructions
SED2 to BT300 Variable Frequency Drives Migration Guide
Document Number 125-1005
January 12, 2015
Siemens Industry, Inc. Page 5
Wiring
Table 1. Conventional Bypass.
SED2
Terminal
Number
Description
Bypass
Terminal
Block Wire
Label
Terminal
Block
BT300 Wire
Color
BT300
Terminal
Number
Description
Function
8 Digital Input 4 108 Blue 9 Digital Input 2 Run Interlock 2
(M2 Status
Coast to Stop)
5 Digital Input 1 105 Blue 8 Digital Input 1 Start Stop
9 24 Vdc + 109 Blue 6 24 Vdc + Power 24 Vdc
22 RO1 NO 7 Red 24 RO2 NC Fault Status
21 RO1 Common 5 Red 25 RO2 Common Fault Status
Table 2. Electronic Bypass.
SED2
Terminal
Number
Description
Bypass
Terminal
Block Wire
Color
Terminal
Block
BT300 Wire
Color
BT300
Terminal
Number
Description
Function
8 Digital Input 4 Purple Blue 14 Digital Input 4 Run Interlock 1
6 Digital Input 2 Yellow Blue 9 Digital Input 2 Run Interlock 2
(M2 Status
Coast to Stop)
5 Digital Input 1 Brown Blue 8 Digital Input 1 Start Stop
28 24 Vdc Blue Blue 7 Ground Power 24 Vdc
25 RO2 NO Red Red 23 RO1 NO Run Status
24 RO2 Common Red Red 22 RO1 Common Run Status
22 RO1 NO Orange Red 24 RO2 NC Fault Status
21 RO1 Common Orange Red 25 RO2 Common Fault Status
Required BT300
Parameter Settings
The BT300 requires some parameter settings to be changed for proper operation of
the Bypass Option (Conventional or Electronic) retrofit on an SED2 Bypass.
The parameter setting changes may be done using the keypad or the Siemens NET
Tool.
See the proper section for the configuration method you wish to use.