Installation Instructions

Document No. 129-703
Installation Instructions
May 10, 2016
Page 4 of 7 Siemens Industry, Inc.
6. Remove the crimped end from the ground cable
and use a wire stripper to strip 3/8" from the end,
if required.
7. Terminate existing bypass wiring (control,
power, and ground) to the bottom edge of the
terminal block assembly. See Figure 14 and
Table 1.
Figure 14. Terminated Bypass Wiring.
Table 1.
Conventional (A)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
108
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
105
8
Digital Input 1
Start Stop
9
24 Vdc +
109
6
24 Vdc +
Power 24 Vdc
22
RO1 NO
7
24
RO2 NC
Fault Status
21
RO1 Common
5
25
RO2 Common
Fault Status
Electronic (E)
SED2
Terminal No.
Description
Bypass Wire
Color
(Number)
BT300
Terminal No.
Description
Function
8
Digital Input 4
Purple
14
Digital Input 4
Run Interlock 1
6
Digital Input 2
Yellow
9
Digital Input 2
Run Interlock 2
(M2 Status
Coast to Stop)
5
Digital Input 1
Brown
8
Digital Input 1
Start Stop
28
24 Vdc -
Blue
7
Ground
Power 24 Vdc
25
RO 2 NO
Red
23
RO1 NO
Run Status
24
RO 2 Common
Red
22
RO1 Common
Run Status
22
RO1 NO
Orange
24
RO2 NC
Fault Status
21
RO1 Common
Orange
25
RO2 Common
Fault Status