Installation Instructions
Document No. 129-710
Installation Instructions
May 10, 2016
Page 4 of 10 Siemens Industry, Inc.
SED2 Frame Size C
WARNING:
Always wait five minutes after disconnecting
the SED2 from the power source before
performing any work.
1. Disconnect power.
2. Remove SED2 terminal strip and drive
protective cover.
Figure 1. SED2 Drive with Covers Removed.
3. Using a small flat-blade screwdriver, disconnect
the control wiring from the drive.
4. Using a small Phillips screwdriver, disconnect
the input power, output motor leads, and ground
conductor at the SED2 Drive terminals.
5. Open thebypass door and pull the wiring down
through the conduits into the cabinet.
Figure 2. Control, Power, and Motor Wiring
Removed.
6. Remove the conduits nuts from the fittings inside
the bypass enclosure.
Figure 3. Conduit Lock Nuts (Typical).
7. Using a No. 2 Phillips screwdriver, remove the
drive mounting screws.
Figure 4. SED2 Drive Mounting Screw Location.
8. Pull the drive and conduits outward and up away
from the enclosure back plate.
9. SED2 Drive removal is complete
SED2 Frame Sizes D and E
WARNING:
Always wait five minutes after disconnecting
the SED2 from the power source before
performing any work.
1. Disconnect power.
2. Remove keypad.